Start, stop and operation of XBC diesel engine fire pump set

18-06-2024

The start, stop and operation of the XBC diesel engine fire pump unit involve several key steps and precautions. The following is a detailed explanation of the process:

1. Inspection work before starting

1. Check the oil level of the fuel tank: Make sure the oil level of the fuel tank is not less than 2/3 in case of emergency.

2. Confirm the valves of the oil inlet pipe and the oil return pipe: Check whether the valves of the oil inlet pipe and the oil return pipe are fully open to ensure that the diesel can enter the diesel engine smoothly.

3. Cooling water check: Check the cooling water level. If the level cannot be seen, add cooling water (desalted water) directly until the overflow pipe is out of water.

4. Bearing cooling water check: Before starting the diesel engine, open the water inlet valve and water outlet valve of the bearing cooling water (if the outlet is not equipped with a valve) to ensure the cooling of the bearing during operation.

5. Bearing lubricating oil check: Check the lubricating oil level in the bearing oil chamber to ensure that it is between 1/3 and 2/3.

6. Gearbox lubricating oil check: Check the lubricating oil level in the gearbox oil chamber to ensure that it meets the requirements of the oil level gauge.

2. Start-up operation

1. Start and stop at the machine side:

After confirming that the diesel engine is ready, select the idle speed on the load switch of the machine side operation panel, set the switch to local, press the start button, and start the diesel engine.

After 3 minutes of starting, the load switch is set to full speed, and the diesel engine runs at the rated speed (such as 1500 rpm).

2. Remote start and stop:

After confirming that the diesel engine is ready, set the selection switch of the machine side operation panel to remote, then go to the corresponding charging control panel, select local, press the start switch for 5S, and the diesel engine starts.

After 3 minutes, press the acceleration button, and the diesel engine automatically increases to the rated speed and runs at full load.

3. Stop operation

1. Machine side parking: first turn to idle operation for 5 minutes and then press the stop button to stop. ,2. Remote parking: first press the deceleration button, and after idling for 5 minutes, press the stop button to stop.

In summary, the start, stop and operation of the XBC diesel engine fire pump group need to follow strict steps and precautions to ensure its safe and efficient operation.

Get the latest price? We'll respond as soon as possible(within 12 hours)

Privacy policy